Description
Key Features & Advantages
Six capacity classes for modular data centers, server rooms and high-density IT environments.
Variable-frequency compressors adapt cooling output to changing IT heat loads.
Electronically commutated fans support efficient and responsive airflow management.
Available in 1100, 1200 and 1400 mm depths for different rack-row layouts.
7-inch touchscreen on 25–60 kW models, with monitoring, alarms and group control functions.
Cooling-only and temperature-and-humidity configurations, subject to model availability.
Typical Applications
Precision cooling integrated into modular IT infrastructure.
Localized cooling for concentrated server and network equipment loads.
In-row deployment alongside IT cabinets and containment systems.
Cooling infrastructure for distributed and regional IT installations.
Configurable cooling for engineered containerized IT solutions.
Environmental control for continuously operated IT environments.
Models & Cooling Capacities
Deckro RowCool Series offers six nominal capacity classes with 300 mm and 600 mm cabinet widths. Each capacity class is available with 1100, 1200 or 1400 mm cabinet depth options.
| Model Series | Cooling Capacity | Cabinet Width | Airflow | Available Depths |
|---|---|---|---|---|
| DRC-IR-012 | 12.5 kW | 300 mm | 2,850 m³/h* | 1100 / 1200 / 1400 mm |
| DRC-IR-025 | 25.5 kW | 300 mm | 5,080 m³/h* | 1100 / 1200 / 1400 mm |
| DRC-IR-030 | 30.8 kW | 300 mm | 5,250 m³/h* | 1100 / 1200 / 1400 mm |
| DRC-IR-040 | 42.8 kW | 600 mm | 8,580 m³/h* | 1100 / 1200 / 1400 mm |
| DRC-IR-050 | 51.5 kW | 600 mm | 10,600 m³/h* | 1100 / 1200 / 1400 mm |
| DRC-IR-060 | 62.7 kW | 600 mm | 11,600 m³/h* | 1100 / 1200 / 1400 mm |
*Airflow figures are taken from the product-family technical reference. Performance for each cabinet-depth variant is subject to final technical confirmation.
Capacity Classes
Depth Options
Indoor Configurations
Technical Specifications
Cooling Technology
- Air-cooled precision cooling
- DC variable-frequency compressor
- EC fan technology
- Electronic expansion valve
- R410A refrigerant
- Variable-capacity operation
Mechanical Configuration
- 300 mm width: 12 / 25 / 30 kW classes
- 600 mm width: 40 / 50 / 60 kW classes
- Depth options: 1100 / 1200 / 1400 mm
- Nominal cabinet height: 2000 mm
- Dual-side supply: 12 kW class
- Front supply: 25–60 kW classes
Control & Monitoring
- 7-inch color touchscreen: 25–60 kW
- 12 kW configuration: without display
- Real-time operating information
- Alarm and parameter management
- Multi-unit group control functionality
- Project-specific integration requirements
Environmental Configuration
- Cooling-only configuration
- Constant temperature and humidity option
- Electric reheating on equipped models
- Humidification: 3 kg/h where equipped
- Standard outdoor condensing units
- Engineered centralized outdoor solutions
Electrical & Environmental Data
| Model | Reheat | Humidifier | Cooling FLA* | Temp. & Humidity FLA* |
|---|---|---|---|---|
| DRC-IR-012 | 3.0 kW | 3.0 kg/h | 19.0 A | 22.9 A |
| DRC-IR-025 | 4.5 kW | 3.0 kg/h | 23.2 A | 27.9 A |
| DRC-IR-030 | 4.5 kW | 3.0 kg/h | 29.2 A | 34.0 A |
| DRC-IR-040 | 6.0 kW | 3.0 kg/h | 30.1 A | 37.6 A |
| DRC-IR-050 | 6.5 kW | 3.0 kg/h | 34.8 A | 42.0 A |
| DRC-IR-060 | 6.5 kW | 3.0 kg/h | 43.8 A | 51.0 A |
*Electrical current values are based on the technical reference and must be verified against the selected configuration before electrical design. Reference supply: 380 V, three-phase with neutral, 50 Hz. Final voltage and frequency compatibility must be confirmed per model.
Outdoor Unit Configurations
Deckro RowCool systems can be supplied with standard outdoor condensing units or project-engineered centralized outdoor configurations.
Standard Outdoor Units
| Deckro Code | Indoor Model | Fans | Net Weight | W × D × H (mm) |
|---|---|---|---|---|
| DRC-ODU-020-S | DRC-IR-012 | 2 | 49 kg | 832 × 330 × 1246* |
| DRC-ODU-040-S | DRC-IR-025 | 1 | 135 kg | 1378 × 982 × 740 |
| DRC-ODU-046-S | DRC-IR-030 | 1 | 139 kg | 1578 × 1275 × 750 |
| DRC-ODU-058-S | DRC-IR-040 | 1 | 150 kg | 1778 × 1275 × 750 |
| DRC-ODU-078-S | DRC-IR-050 | 2 | 176 kg | 2178 × 1275 × 740 |
| DRC-ODU-090-S | DRC-IR-060 | 2 | 185 kg | 2378 × 1275 × 750 |
*The 12 kW outdoor-unit dimensions differ between source documents. All outdoor dimensions and weights require confirmation against the final approved drawings.
Centralized Outdoor Units
| Deckro Code | Fans | Net Weight | W × D × H (mm) |
|---|---|---|---|
| DRC-ODU-046-C | 1 | 140 kg | 1098 × 1098 × 1684 |
| DRC-ODU-058-C | 1 | 150 kg | 1098 × 1098 × 1684 |
| DRC-ODU-068-C | 1 | 166 kg | 1098 × 1098 × 1774 |
| DRC-ODU-078-C | 1 | 176 kg | 1098 × 1098 × 1774 |
| DRC-ODU-090-C | 1 | 186 kg | 1298 × 1098 × 1774 |
| DRC-ODU-098-C | 1 | 196 kg | 1298 × 1098 × 1774 |
Centralized outdoor units are not assigned on a one-to-one basis. Selection, refrigerant piping and system compatibility require project-specific engineering verification.
Product Codes & Ordering Information
Indoor unit codes identify cooling capacity, environmental configuration and cabinet depth.
Deckro RowCool / 25 kW Class / Temperature & Humidity / 1200 mm Depth
| Capacity Class | Temperature & Humidity | Cooling Configuration* |
|---|---|---|
| 12 kW | DRC-IR-012-H-D11 / D12 / D14 | DRC-IR-012-C-D11 / D12 / D14 |
| 25 kW | DRC-IR-025-H-D11 / D12 / D14 | DRC-IR-025-C-D11 / D12 / D14 |
| 30 kW | DRC-IR-030-H-D11 / D12 / D14 | DRC-IR-030-C-D11 / D12 / D14 |
| 40 kW | DRC-IR-040-H-D11 / D12 / D14 | DRC-IR-040-C-D11 / D12 / D14 |
| 50 kW | DRC-IR-050-H-D11 / D12 / D14 | DRC-IR-050-C-D11 / D12 / D14 |
| 60 kW | DRC-IR-060-H-D11 / D12 / D14 | DRC-IR-060-C-D11 / D12 / D14 |
D11 = 1100 mm; D12 = 1200 mm; D14 = 1400 mm.
H = constant temperature and humidity.
C = cooling configuration.
*The 12 kW C configuration requires final confirmation of its temperature-control functions.
Standard outdoor unit codes: DRC-ODU-020-S, DRC-ODU-040-S, DRC-ODU-046-S, DRC-ODU-058-S, DRC-ODU-078-S and DRC-ODU-090-S.
Centralized outdoor unit codes: DRC-ODU-046-C, DRC-ODU-058-C, DRC-ODU-068-C, DRC-ODU-078-C, DRC-ODU-090-C and DRC-ODU-098-C.
Engineering & Project Integration
Deckro RowCool systems are selected according to the project cooling load, rack arrangement, airflow direction, outdoor ambient conditions and refrigerant piping requirements.
Final equipment dimensions, electrical characteristics, outdoor unit selection, operating conditions and configuration-specific performance must be confirmed through the approved technical documentation before ordering.
Configure Your Deckro RowCool Solution
Contact Deckro for model selection, cabinet depth options, outdoor unit configuration, technical documentation and project-specific quotations.