Description
Key Features & Advantages
True Online Double Conversion
DSP-controlled UPS with 3-Level topology for stable, clean output power in critical loads.
1.0 Output Power Factor
PF=1.0 output for maximum usable kW capacity and better load compatibility.
High Efficiency
Up to 94.5% efficiency (typ.) and up to 98% in ECO mode for reduced operating cost.
Wide Input Range
110–288 Vac input voltage range and 40–70 Hz frequency range, generator friendly.
Smart Battery Management
Hot-swap battery support, intelligent charging and configurable battery count (16–20).
Flexible Installation
Rack & Tower usage flexibility with LCD+LED user interface and multiple comm. options.
Typical Applications
Data Centers & IT Rooms
Servers, network, storage, security appliances, edge IT and comms.
Telecommunications
Transmission rooms, base stations, NOC rooms, small shelters.
Hospitals & Healthcare
Critical electronics, labs, imaging support and building ICT.
Banks & Financial Institutions
Branch IT continuity, network rooms and secure operations.
Industrial Facilities
Automation, control panels, instrumentation and process IT.
Offices & Business Centers
Core network, small server rooms, security systems and AV.
Models & Configurations
Deckro PowerOne RT Series covers 1–10 kVA capacity range with rack/tower flexibility and optional long-run battery configurations.
| Model | Capacity | Input | Output | Battery (DC) |
|---|---|---|---|---|
| PowerOne+ 101RT | 1 kVA | 208/220/230/240 Vac, PF 0.99, THDi ≤ 5% | Sine wave, PF 1.0, THD ≤ 1% (linear) | 192 Vdc (adj. 192–240), 16–20 batteries |
| PowerOne+ 103RT | 3 kVA | 110–288 Vac range, 40–70 Hz | ±1% regulation, crest factor 3:1 | 192 Vdc (adj. 192–240), 16–20 batteries |
| PowerOne+ 105RT | 5 kVA | Bypass range -40% ~ +15% (adjustable) | Overload up to 150% (short duration) | 192 Vdc (adj. 192–240), 16–20 batteries |
| PowerOne+ 106RT | 6 kVA | Single phase input, APFC up to 0.99 | 50/60Hz ±0.1% in battery mode | 192 Vdc (adj. 192–240), 16–20 batteries |
| PowerOne+ 110RT | 10 kVA | Wide input range, generator compatible | Sine wave, PF 1.0, THD ≤ 4% (non-linear) | 192 Vdc (adj. 192–240), 16–20 batteries |
1–10
kVA capacity range
0 ms
transfer time (online)
4
parallel connections (max)
Input Specifications
- Input wiring: 1F – 3 wire (F + N + T)
- Nominal voltage: 208 / 220 / 230 / 240 Vac
- Voltage range: 110–176 Vac (linear derating 50–100% load); 176–288 Vac (no derating)
- Frequency: 50/60 Hz auto sensing
- Frequency range: 40–70 Hz
- Input PF: up to 0.99
- THDi: ≤ 5%
- Bypass voltage range: -40% ~ +15% (adjustable)
Output Specifications
- Output wiring: Single phase (F – N)
- Output voltage: 208 (PF=0.9) / 220 / 230 / 240 Vac
- Voltage regulation: ±1%
- Frequency: synchronized to bypass (mains); 50/60 Hz ±0.1% (battery)
- Waveform: Sine wave
- Output PF: 1.0
- THD: ≤ 1% (linear); ≤ 4% (non-linear)
- Crest factor: 3:1
- Overload: 105–110% / 10 min, 110–125% / 1 min, 126–150% / 30 sec
Battery & Charging
- DC voltage: 192 Vdc (adjustable 192–240 Vdc)
- Battery count: 16 units (adjustable 16–20)
- Hot-swap battery support
- Charging current: Standard model 1A; Long-run 5A (default) adjustable 1–5A; optional up to 12A
- Charging time: Standard 90% in ~8 hours; long-run depends on external battery
- Smart charging: float/equalization control, charger sleep control (battery life improvement)
System & Environment
- Transfer time: 0 ms
- Protections: short circuit, overload, over temperature, battery low/over/under voltage, fan failure
- Parallel connections: up to 4
- Communication: RS232 (standard); optional USB / RS485 / dry contacts / SNMP / battery temp comp.
- Display: LCD + LED
- Operating temperature: 0°C ~ 40°C
- Storage temperature: -25°C ~ 55°C (without battery)
- Humidity: 0 ~ 95% (non-condensing), IP class: IP20
- Altitude: ≤1000 m (1% derating per additional 100 m)
Product Codes
| Model Code | Product Description | Capacity | Form Factor | Battery Type |
|---|---|---|---|---|
| PowerOne+ 101RT | Online UPS, DSP + 3-Level, PF=1.0, Rack/Tower | 1 kVA | Rack/Tower | Internal (standard) / External (long-run) |
| PowerOne+ 103RT | Online UPS, wide input range, hot-swap support | 3 kVA | Rack/Tower | Internal (standard) / External (long-run) |
| PowerOne+ 105RT | Online UPS, PF=1.0 output, ECO mode up to 98% | 5 kVA | Rack/Tower | Internal (standard) / External (long-run) |
| PowerOne+ 106RT | Online UPS, strong overload capability, multiple interfaces | 6 kVA | Rack/Tower | Internal (standard) / External (long-run) |
| PowerOne+ 110RT | Online UPS, max performance for IT and data center loads | 10 kVA | Rack/Tower | Internal (standard) / External (long-run) |
Note: Standard vs Long-run model options depend on battery configuration and charger rating.
Need a reliable UPS for your critical IT infrastructure?